DA-13-012 (RP-1344) — Cleanroom Pressurization Strategy Update–Quantification and Validation of Minimum Pressure Differentials when Using Auxiliary Devices (Part 2)

Click here to purchase

Pressurization technology utilized in cleanroom facilities is typically used to minimize airborne contamination from less-clean rooms into a cleaner room. Pressurization design has been traditionally based on intuitive suggestion instead of well-established guidelines. A pressure differential of 0.05 in. (12.5 Pa) as a single and uniform criterion is believed to be oversimplified for more complex conditions, such as when an auxiliary device is utilized inside a cleanroom.

As the second part of the research, the research team quantitatively evaluated the effectiveness of common auxiliary devices in room cleanliness control, such as a clean bench, a mini-environment, a containment hood, and a pressure stabilizer. It was found that some of these devices could contribute to a possible reduction in room cleanliness requirements, air change rates, or pressure differential values, while others may not. A summarized table is included as a general recommendation, along with the minimum pressure differential table listed in Part 1 of this research (Sun 2013).