CSA C22.2 NO. 2515-09 (R2014)

Click here to purchase
Preface

This is the common CSA and UL standard for aboveground reinforced thermosetting resin conduit (RTRC) and fittings. It is the first edition of CSA C22.2 No. 2515, and the first edition of UL 2515. Previously, requirements for aboveground RTRC were found in the common CSA and UL Standard for Reinforced Thermosetting Resin Conduit and Fittings. This edition of CSA C22.2 No.2515 supersedes the fourth edition of CSA C22.2 No. 211.3-96 last revised on June 1, 1997, for products covered in this standard, as indicated in the scope of this standard. This edition of UL 2515 supersedes the third edition of UL 1684 last revised on August 11, 2004.

Scope

1.1 This Standard specifies the requirements for low-halogen aboveground (Type AG) reinforced thermosetting resin conduit (RTRC) and fittings for installation and use in accordance with CSA C22.1, Canadian Electrical Code (CEC), Part I, and NFPA 70, National Electrical Code (NEC), in non-hazardous locations.

1.2 The products specified in this Standard are intended for use at -40°C (-40°F) to 110 °C (230°F). The products are for use above ground in exposed and concealed locations. The products are also suitable for use below ground by direct burial or by encasement in concrete.

1.3 Type AG conduit has not been evaluated for directional boring applications.

1.4 This Standard covers ID (dimensions based on inside diameters) and IPS (dimensions based on outside diameters of iron pipe sizes) conduit and fittings. Trade sizes (metric designators) are 1/2 (16) to 6 (155).

Note: The values in parenthesis are metric size designations of conduits and fittings and do not necessarily reflect metric trade sizes.

1.5 ID and IPS conduit are designated as SW (Standard Wall) or HW (Heavy Wall), which refer to specific wall thicknesses.

1.6 Fittings specified in this Standard include, but are not limited to, straight couplings, 5°angle couplings, adapters, and elbows with plain ends or integral belled ends at one or both ends, expansion joints, and conduit bodies.

Note: In Canada, conduit bodies are not evaluated as outlet boxes – they are fittings. Requirements in this standard for conduit bodies intended for use as outlet boxes do not apply in Canada. In the United States, a conduit body may be used as an outlet box for the splicing of conductors.

Product Details

Edition:
1st
Published:
07/01/2009
ISBN(s):
1553970586
Number of Pages:
70
File Size:
1 file , 1.5 MB
Product Code(s):
2419732, 2419732