DE-13-023 — Assessment of Burning Velocity Test Methods for Mildly Flammable Refrigerants, Part 2: Vertical-Tube Method (RP-1583)
- Comments Off on DE-13-023 — Assessment of Burning Velocity Test Methods for Mildly Flammable Refrigerants, Part 2: Vertical-Tube Method (RP-1583)
- ASHRAE
This paper is based on findings resulting from ASHRAE Research Project RP-1583.
For further development of refrigerant safety standards, burning velocity(Su)measurements of R-32/air and R-32/134a/air flames were carried out by the vertical-tube method with a 40mm (1.6in.) diameter tube, and the precision and measurable lower limit of the test method were investigated. To evaluate the precision of the test method, we obtained the ideal (buoyancy-free and with no conductive heat loss to the wall) burning velocities of these refrigerants by the spherical-vessel method in microgravity.
Product Details
- Published:
- 2013
- Number of Pages:
- 10
- File Size:
- 1 file , 2.5 MB